Converter · ASTM B258 · IEC 60228

AWG to mm² converter

Wire gauge to metric cross-section, both directions — plus the IEC cable size you actually order, DC resistance, and the NEC ampacity reference. Type in any field; everything updates.

Last updated: October 2026

Converter · ASTM B258 · IEC 60228

AWG ↔ mm² ↔ kcmil

Type in any field — the others update. Shows the metric cable to order and NEC ampacity.

Quick presets

AWG to mm² — formula and table

AWG dimensions come from ASTM B258: diameter in mm = 0.127 × 92(36−n)/39, where n is the gauge number (4/0 = −3, 3/0 = −2, 2/0 = −1, 1/0 = 0). Area follows from the circle: mm² = π/4 × d². Kcmil = circular mils ÷ 1000, and 1 kcmil = 0.5067 mm² exactly. The converter above runs these identities in both directions and rounds to the nearest gauge when you start from mm².

Field reality: the converted number is never what you buy

12 AWG converts to 3.31 mm² — but no cable is manufactured in 3.31 mm². Metric cable follows the IEC 60228 series (1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120 …), so the converter rounds up to the smallest standard size that is not smaller (4 mm² for 12 AWG, +21% copper). Cable is verified by DC resistance per kilometre, not by measuring copper: 12 AWG at ~5.21 Ω/km clears the 2.5 mm² limit (7.41 Ω/km) but the safe order is 4 mm² (4.61 Ω/km limit).

Diameter vs area — which one do you need?

Diameter (mm) is for physical hardware: glands, ferrules, lug barrels, drill sizes, conduit fill. Area (mm²) is for documents: cable schedules, ampacity, voltage drop, purchase orders. Stranded cable of the same nominal size measures wider than solid (air between strands) — Class 5 flexible at 4 mm² runs 3.0 mm max vs 2.4 mm solid — so size glands from the manufacturer overall diameter, never the solid conversion figure.

FAQ

AWG conversion questions, answered

What size metric cable do I order for 12 AWG?

12 AWG converts to 3.31 mm², but no cable is made in that size. Order 4 mm² IEC cable — the smallest standard size that is not smaller (+21% copper). The 4 mm² resistance limit (4.61 Ω/km) clears 12 AWG comfortably.

Is AWG diameter the same as AWG area in mm?

No. 12 AWG is 2.05 mm across (diameter) with 3.31 mm² cross-section (area). Use diameter for glands, lugs, and drill sizes. Use area for cable specs, ampacity, and purchase orders.

How do I convert kcmil to mm²?

Multiply kcmil by 0.5067. So 250 kcmil = 126.7 mm², 500 kcmil = 253.4 mm². Reverse: divide mm² by 0.5067 to get kcmil.

Does aluminum use the same AWG table?

Dimensions are identical — AWG describes conductor size regardless of metal. What changes is resistance (≈61% higher for Al) and ampacity (Table 310.16 aluminum columns). Size aluminum one to two gauges larger for equal current.

Does this converter work offline?

Yes. FieldCalc is an installable PWA — after your first visit, this converter runs with zero signal. All math stays on your device.

Related converters: HP to kW ·kW to BTU/hr ·All converters

Next step: check ampacity in the wire-size calculator ·check conduit fill ·NEC wire-size chart