Reference · NEC 2023 Table 310.16 · 75°C terminals

Wire size chart — what size for your amps

Minimum copper and aluminum at base conditions (≤3 conductors, 30°C ambient) with 240.4(D) breaker caps already applied. Hot attic, bundled conduit, or a long run? Read the derating rows below, then verify with the calculator.

LoadCopper minAluminum minBreakerTypical useHeadroom pick
15A lighting#14 Cu (20A)#12 Al (20A)15ALighting branch circuits#12 Cu
20A receptacle#12 Cu (25A)#10 Al (30A)20AGeneral receptacles, kitchen small-appliance#10 Cu
30A dryer / WH#10 Cu (35A)#8 Al (40A)30ADryer, water heater#8 Cu
40A range#8 Cu (50A)#8 Al (40A)40ARange, large appliance#6 Cu
50A EV / RV#6 Cu (65A)#6 Al (50A)50AEV charger, RV outlet (check 125% if continuous)#6 Cu · #4 Al
60A subpanel#6 Cu (65A)#4 Al (65A)60AWorkshop / garage subpanel#4 Cu
100A feeder#3 Cu (100A)#1 Al (100A)100ASubpanel, small service#2 Cu · #1/0 Al
150A feeder#1/0 Cu (150A)#3/0 Al (155A)150ALarge subpanel / service#2/0 Cu
200A service#3/0 Cu (200A)#250 Al (205A)200AResidential service entrance#4/0 Cu · #300 Al

When the chart minimum isn't enough

Hot attic: #10 → ~29A

#10 THHN at 104°F with 6 conductors: 40 × 0.91 × 0.80 = 29.1A — a 30A load needs #8. Attics hit 122°F where the factor drops to 0.75.

Continuous loads ×125%

EV chargers and heaters running 3+ hours: 50A × 1.25 = 62.5A → #6 Cu minimum. The breaker is sized to the continuous load, not the other way around.

Bundled conduit derates fast

4–6 conductors ×0.80 · 7–9 ×0.70 · 10–20 ×0.50. Four circuits in one pipe turn #12's 30A (90°C start) into 24A before the terminal cap.

Long runs fail drop first

20A at 120V on #12 passes ampacity but exceeds 3% past ~60ft one-way. Ampacity and drop are independent — the larger wire wins.

Wire size questions, answered

20A circuit — what size?

#12 copper (25A, 20A breaker). #14 is capped at 15A per 240.4(D) and cannot serve 20A.

30A dryer — what size?

#10 copper (35A, 30A breaker). Aluminum needs #8.

100A subpanel — what size?

#3 Cu / #1 Al minimum; installers usually pull #2 Cu / #1/0 Al for headroom.

200A service — what size?

#3/0 Cu / 250 kcmil Al minimum; #4/0 Cu / 300 Al is the common default.

EV charger on 50A?

Size at 125%: 62.5A → #6 Cu minimum, then check drop for the run length.

Copper vs aluminum?

Al needs 1–2 sizes larger for equal ampacity. Use AL-rated lugs and antioxidant; avoid Al for 15–20A branches.

Size my exact load →Worked examples →Table 310.16 →

Related: Ampacity vs voltage drop ·Conduit fill chart ·All electrical calculators