Ampacity vs voltage drop

Two independent checks. The wire must pass both. Short runs are ampacity-governed; long runs are drop-governed.

1 · Ampacity = heat (mandatory)

Table 310.16 limits current so insulation stays below 60/75/90°C. Derate for heat (ambient) and bundling, cap at terminals per 110.14(C), cap breakers per 240.4(D). This is Code — inspectors enforce it.

2 · Voltage drop = performance (recommended)

NEC informational notes recommend ≤3% branch, ≤5% total (feeder + branch). Not Code-enforceable in most jurisdictions, but motors stall, lights dim, and electronics fault when drop is high. Formula: 2·K·I·L/CM single-phase (K=12.9 Cu, 21.2 Al, L = one-way feet).

Rule of thumb

Check both in the calculator →Worked examples →