Reference · IBC 2024 Table 1604.3

Allowable deflection limits

Codes limit deflection as a fraction of span — L/360 means sag ≤ span ÷ 360. These are serviceability limits (cracking, bounce, finishes), checked against live load alone or total load depending on the row.

ApplicationLimit12 ft allows20 ft allows
Floor, live load onlyL/3600.40 in (10.2 mm)0.667 in (16.9 mm)
Floor / roof, total (D+L)L/2400.60 in (15.2 mm)1.000 in (25.4 mm)
Tile / plaster / brittleL/4800.30 in (7.6 mm)0.500 in (12.7 mm)
Roof, no ceilingL/180–L/1200.80 in (20.3 mm)1.333 in (33.9 mm)
Masonry / glass wallsL/6000.24 in (6.1 mm)0.400 in (10.2 mm)
Cantilever armL/1800.80 in per 12ft armcheck at 2× length

Live vs total — which governs?

Check both: L/360 under live load alone, L/240 under dead + live together. Light residential floors usually fail L/360 first; heavy roofs and long tile floors fail total-load or L/480 first. Tile manufacturers often demand L/720 — stricter than code.

Cantilever footnote

Some codes measure the cantilever limit against twice the arm length (a 10 ft arm checked as L = 20 ft → 1.333 in at L/180). The calculator reports the raw tip deflection and L/δ so you can apply either reading.